Chapter 2 Specifications
2-29
Pulse/PWM Output Specifications
DIO Standard Input/Output is used as a Pulse Output or PWM Output. The setup is done by the GP-Pro EX.
GP-Pro EX Reference Manual “Controlling External I/O”
Pulse Output PWM Output
Output Points 4 Points
Output Method
PLS0 to PLS3 (OUT0 to
OUT3) defined by user
PWM0 to PWM3 (OUT0 to
OUT3) defined by user
Load Voltage DC24V
Min. Load Current 1mA
Max. Output Frequency Up to 65kHz possible per point (set through software)
Pulse Acceleration/
Deceleration Speed
Available
ON Duty 50%±10% (at 65kHz)
*1
*1 The ON Duty error (10%) will be reduced if the Output frequency is low.
19 to 81% (at 65kHz)
*2
*2 The ON Duty (effective range) will be widened if the Output frequency is low.